EICR Remedial Works – Dartford
EICR Remedial Works – Dartford

Following an unsatisfactory EICR for a landlord in Dartford, further fault-finding identified that all CPCs (earth conductors) had been cut at the living room lighting point, resulting in no R1+R2 readings throughout the lighting circuit. The wiring was correctly re-terminated using Wago connectors, the installation was neatened up, and the circuit was fully retested, achieving a satisfactory R1+R2 result and restoring the circuit to a safe condition.